"phase": "phase2",
"pack_count": 2,
"bank_discharge_A_12kW": 249.3,
"bank_demand_A": 249.3,
"per_pack_discharge_A": 124.7,
"bank_limit": {
"name": "inverter max discharge",
"A": 250,
"headroom_A": 0.7
},
"per_pack_limits_A": {
"JK-BMS OCP trip (300s)": 150,
"EVE cell-honest (0.5P)": 157,
"JK-BMS marketed max": 200
},
"per_pack_binding": {
"name": "JK-BMS OCP trip (300s)",
"A": 150,
"headroom_A": 25.3
},
"per_pack_discharge_C": 0.397,
"per_pack_charge_C": 0.398,
"surge_bank_A": 280.5,
"surge_per_pack_A": 140.3,
"surge_note": "2-pack split keeps per-pack surge 140A under the 150A/300s BMS OCP even over the 18kPV's 10-min peak window (the single-pack Phase-1 case relied on the 3.5s 6000XP surge being too brief).",
"bank_usable_kwh": 32.16,
"bank_usable_kwh_80dod": 25.73,
"runtime_12kw_80dod_h": 2.14,
"days_at_avg_load": 0.77,
"days_at_aug_peak": 0.48,
"per_pack_classT_fuse_A": 175,
"per_pack_cable_AWG": "2/0",
"per_pack_cable_ampacity_A": 175,
"bank_aggregate_fuse_A": 350,
"bank_cable_single_AWG": "400",
"fuse_cable_ok": true,
"verdict": "PASS",
"comms_note": "2 packs: JK-BMS master/slave, one master -> 18kPV via CAN (single link). 18kPV native closed-loop is EG4-48V; Docan/JK via a CAN profile \u2014 confirm on arrival. Open-loop fallback fully viable (no battery-life penalty)."
}