  "phase": "phase2",
  "pack_count": 2,
  "bank_discharge_A_12kW": 249.3,
  "bank_demand_A": 249.3,
  "per_pack_discharge_A": 124.7,
  "bank_limit": {
    "name": "inverter max discharge",
    "A": 250,
    "headroom_A": 0.7
  },
  "per_pack_limits_A": {
    "JK-BMS OCP trip (300s)": 150,
    "EVE cell-honest (0.5P)": 157,
    "JK-BMS marketed max": 200
  },
  "per_pack_binding": {
    "name": "JK-BMS OCP trip (300s)",
    "A": 150,
    "headroom_A": 25.3
  },
  "per_pack_discharge_C": 0.397,
  "per_pack_charge_C": 0.398,
  "surge_bank_A": 280.5,
  "surge_per_pack_A": 140.3,
  "surge_note": "2-pack split keeps per-pack surge 140A under the 150A/300s BMS OCP even over the 18kPV's 10-min peak window (the single-pack Phase-1 case relied on the 3.5s 6000XP surge being too brief).",
  "bank_usable_kwh": 32.16,
  "bank_usable_kwh_80dod": 25.73,
  "runtime_12kw_80dod_h": 2.14,
  "days_at_avg_load": 0.77,
  "days_at_aug_peak": 0.48,
  "per_pack_classT_fuse_A": 175,
  "per_pack_cable_AWG": "2/0",
  "per_pack_cable_ampacity_A": 175,
  "bank_aggregate_fuse_A": 350,
  "bank_cable_single_AWG": "400",
  "fuse_cable_ok": true,
  "verdict": "PASS",
  "comms_note": "2 packs: JK-BMS master/slave, one master -> 18kPV via CAN (single link). 18kPV native closed-loop is EG4-48V; Docan/JK via a CAN profile \u2014 confirm on arrival. Open-loop fallback fully viable (no battery-life penalty)."
}