"discharge_A_6kW": 126.0,
"limits_A": {
"inverter max discharge": 140,
"JK-BMS OCP trip (300s)": 150,
"EVE cell-honest (0.5P)": 157,
"JK-BMS marketed max": 200
},
"binding_limit": {
"name": "inverter max discharge",
"A": 140,
"headroom_A": 14.0
},
"discharge_C": 0.401,
"charge_C_pv": 0.398,
"surge_A": 252.0,
"surge_note": "transient only; one pack cannot sustain >6kW continuously \u2014 Phase-2 second pack relieves surge headroom",
"runtime_full_h": 2.68,
"runtime_full_80dod_h": 2.14,
"runtime_1p5kw_80dod_h": 8.6,
"classT_fuse_A": 175,
"cable_AWG": "2/0",
"cable_ampacity_A": 175,
"fuse_cable_ok": true,
"verdict": "PASS"
}