  "discharge_A_6kW": 126.0,
  "limits_A": {
    "inverter max discharge": 140,
    "JK-BMS OCP trip (300s)": 150,
    "EVE cell-honest (0.5P)": 157,
    "JK-BMS marketed max": 200
  },
  "binding_limit": {
    "name": "inverter max discharge",
    "A": 140,
    "headroom_A": 14.0
  },
  "discharge_C": 0.401,
  "charge_C_pv": 0.398,
  "surge_A": 252.0,
  "surge_note": "transient only; one pack cannot sustain >6kW continuously \u2014 Phase-2 second pack relieves surge headroom",
  "runtime_full_h": 2.68,
  "runtime_full_80dod_h": 2.14,
  "runtime_1p5kw_80dod_h": 8.6,
  "classT_fuse_A": 175,
  "cable_AWG": "2/0",
  "cable_ampacity_A": 175,
  "fuse_cable_ok": true,
  "verdict": "PASS"
}